Overseas Office

M/s Krishna Overseas, Teku,
Machali, Kathmandu, Nepal

Proprietor Mr. Ravi Agarwal
Mob : +977 9851037852

Inverter / UPS - Low Maintenance Battery

Brand Name : STAR PLUS
As per Specification: IS 13369 : 1992

Technical Data :
Type Capacity at
C20 rate (Ah)
Nominal
Voltage (V)
Dimensions (in mm) Type of Container Weight ( in Kg.) Filling Sp. Gr.
at 27°C
Final Sp. Gr.
at 27°C
Length Width Height (OA) Dry Filled
6TP 135 N 200J 135 12 516 ± 5 273 ± 5 294 ± 5 PPCP 30 ± 5% 55 ± 5% 1.225±0.005 1.250±0.005
6TP 150 N 200J 150 12 516 ± 5 273 ± 5 294 ± 5 PPCP 31 ± 5% 56 ± 5% 1.225±0.005 1.250±0.005
6TP 150 IT 150 12 501 ± 5 189 ± 5 430 ± 5 PPCP 26 ± 5% 58 ± 5% 1.225±0.005 1.250±0.005
6TP 165 IT 165 12 501 ± 5 189 ± 5 430 ± 5 PPCP 30 ± 5% 60 ± 5% 1.225±0.005 1.250±0.005
6TP 200 IT 200 12 501 ± 5 189 ± 5 430 ± 5 PPCP 36 ± 5% 63 ± 5% 1.225±0.005 1.250±0.005
6TP 240 IT 240 12 501 ± 5 189 ± 5 430 ± 5 PPCP 41 ± 5% 68 ± 5% 1.225±0.005 1.250±0.005
Summary of Different Charging Modes :
Type Initial Charge Limiting Current (Amps.) Normal Charge Limiting Current(Amps.) Boost Amps. & Hrs. Trickle Amps. Max. Electrolyte Temp. Allow
Short Period Continuously
6TP 135 N 200J 7.92 for 75 hrs. 10.8 for 15 hrs. 1.5 times of the normal rate of charging 135 mA 54°C 48°C
6TP 150 N 200J 8.80 for 75 hrs. 12.0 for 15 hrs. 150 mA 54°C 48°C
6TP 150 IT 8.80 for 75 hrs. 12.0 for 15 hrs. 150 mA 54°C 48°C
6TP 165 IT 9.50 for 75 hrs. 13.2 for 15 hrs.. 165 mA 54°C 48°C
I6TP 200 IT 11.50 for 75 hrs. 16.0 for 15 hrs. 200 mA 54°C 48°C
6TP 240 IT 14.00 for 75 hrs. 19.2 for 15 hrs. 240 mA 54°C 48°C