Marketed by Sen & Co.

Head Office

130, Balaram Dey Street
Near Girish Park metro Station
Kolkata - 700006

Phone: 2530 4492 / 9207
2533 5504 / 6529 5805
Fax: 2533 6734

Inverter / UPS - Low Maintenance Battery

Brand Name : IDEAL
As per Specification: IS 13369:1992

Technical Data :
Type Capacity at
C20 rate (Ah)
Nominal
Voltage (V)
Dimensions (in mm) Type of Container Weight ( in Kg.) Filling Sp. Gr.
at 27°C
Final Sp. Gr.
at 27°C
Volume per Cell(in Litres)
Length Width Height (OA) Dry Filled
IT 500 PLUS 160 12 501 ± 5 189 ± 5 430 ± 5 PPCP 30.0 ± 5% 60.0 ± 5% 1.225±0.005 1.245±0.005 24
IT600 PLUS 190 12 501 ± 5 189 ± 5 430 ± 5 PPCP 36.0 ± 5% 63.0 ± 5% 1.225±0.005 1.245±0.005 23
IT 700 PLUS 220 12 501 ± 5 189 ± 5 430 ± 5 PPCP 41.0 ± 5% 68.0 ± 5% 1.225±0.005 1.245±0.005 22
Summary of Different Charging Modes :
Type Initial Charge Limiting Current (Amps.) Normal Charge Limiting Current(Amps.) Boost Amps. & Hrs. Trickle Amps. Max. Electrolyte Temp. Allow
Short Period Continuously
IT 500 PLUS 8.8 for 75 Hrs. 12.0 for 15 Hrs. 1.5 times of the normal rate of charging 160mA 54°C 48°C
IT 600 PLUS 10.6 for 75 Hrs. 15.0 for 15 Hrs. 1.5 times of the normal rate of charging 190mA 54°C 48°C
IT700 PLUS 13.0 for 75 Hrs. 18.0 for 15 Hrs. 1.5 times of the normal rate of charging 220mA 54°C 48°C
Recharging through Inverter at constant potential mode of 14.4V with limited current as specified. After battery potential reaches 14.4V, the battery should continue in trickle charge mode at constant potential of 13.8V.